The nitrogen cylinder assembly stores nitrogen pressurized to 60/70/80 bar at 21°C that is used as propellent for FM-200™/ HFC-227ea extinguishing agent contained in a separate PFS agent cylinder assemblies.
TECHNICAL INFORMATION
- Approvals for use with EFS/PFS: UL
- Approvals for cylinder: DOT-3AA
- Fill pressure: 60/70/80 bar (870/1015/1160 psi)
- Cylinder rated working pressure: 147 bar (2133 psi)
- Cylinder hydrostatically tested at: 245 bar (3555 psi)
- Cylinder material: Seamless Mn Steel
- Paint specification: Gray polyester powder coated
- Installation position: Vertical
See corresponding datasheets for more technical information on the discharge valves and pressure gauges